Experimental Evaluation of the Heat Output/Input and Coefficient of Performance Characteristics of a Chemical Heat Pump in the Periodic Operation of CaCl2 Hydration ()
1. Introduction
The development of technologies and systems for enhancing energy efficiency to mitigate CO2 emissions has received increasing attention in recent years [1] [2] [3]. Utilizing waste heat discharged from industrial processes is one of the essential issues for improving energy efficiency. Reducing the quantitative, temporal, topographic, and qualitative imbalances remaining between the heat supply and the heat demand is important for promoting heat energy utilization, and many thermal management technologies have been developed. For example, processes and technologies such as the organic rankine cycle [4], thermoelectric power generation [5] [6], heat pumps [7], sensible heat storage [8], and chemical heat pumps have been reported.
Among these technologies, the chemical heat pump (CHP), driven by reversible chemical reactions, is a promising technology for contributing to the need to utilize thermal energy. Studies have suggested a number of natural high-affinity refrigerant and reactant pairs, including H2O [9], NH3 [10], and CO2 [11] for refrigerants and solid oxides and metal halides for reactants. To date, CHPs have been investigated in a number of cycle modes, namely heat storage, heat upgrading, and chiller heat modes.
Many thermal applications using CaCl2 have been demonstrated extensively [12] [13]. This material has the outstanding features of low cost, nontoxicity, and thermochemical stability. The CaCl2/H2O reaction system has been studied for thermochemical heat storage, and the potential use of both the CaCl2/H2O reversible reactions has been demonstrated in previous studies [14] [15] [16].
For heat upgrading, we selected the hydration reaction of CaCl2 for a CHP reaction system, where the reversible hydration reaction is as follows:
(1)
In this study, we examined the chemical heat pump shown in Figure 1. For each batch operation of the heat release operation and the heat storage operation, to constitute an increase of the heat pump mode, we evaluated the output performance using a laboratory scale reactor on the condition of assuming warm water output of around 90˚C. The output per volume of the reactor and the coefficient of performance (COP) were estimated from the result.
2. Experimental and Calculation Approach
2.1. Experimental Set up
A schematic drawing of the experimental setup is provided in Figure 2. The setup comprised three decompression chambers, an evaporator, a condenser, and a reactor with a heat storage module installed inside the reactor chamber. Each of these components was connected with vapor flow tubes. The components and vapor flow tubes were covered with glass wool and a combination of glass wool and electric heaters, respectively, to prevent vapor condensation or heat loss. Each component was also connected to a thermostat bath as a heat source. The heat-medium fluids supplied from the thermostat baths were circulated through the components. Figure 3 shows the corrugated aluminum fin-type heat exchanger used as the heat storage module in the experiments. The heat storage module had a whole volume of 1.1 L and measured 250 mm × 200 mm × 20 mm (without the header). The pitch of the fluid flow path was 8 mm, and the pitch of
Figure 1. Schematic of the chemical heat pump.
Figure 2. Schematic of the experimental apparatus.
Figure 3. The corrugated aluminum fin-type heat exchanger.
the corrugated fin was 3.0 mm. The heat storage module was filled with 650 g of anhydrous CaCl2 particles, covered on the top and bottom with nickel mesh, and installed in the reactor chamber. The filling fraction based on the filling space was 0.42. Reagent anhydrous CaCl2 particles (>95% purity) were obtained from Wako Chemicals (Japan). The material was dried in an electric furnace at 180˚C for 24 hours. The CaCl2 powder was homogenized by diameter (dp = 125 - 250 μm) before filling it into the heat storage module. As a final step before initiating the experiments, air was removed from the three components and the vapor flow tubes by vacuum pump.
In the following experiments, evaluation parameters were calculated based on the experimental results of the heat-medium fluid temperature and the flow rate through the reactor. The fluid temperatures at the heat storage module’s inlet and outlet were measured using platinum resistance temperature detectors, and the fluid flow volume was measured using a turbine flow meter from Japan Flow Controls Co., Ltd. (Japan). Thermal H350 fluid, obtained from JULABO (Germany), was used as the heat-medium fluid in the reactor. Water was used in the evaporator and the condenser. The evaluation parameters, including average volumetric power density, Qave, conversion ratio, X, and cumulative heat capacity, Qcum, were calculated using following equations:
(2)
(3)
(4)
The discharging and charging conditions were selected assuming conversion of the low-temperature waste heat (~200˚C) to heat-enhanced hot water (upward of 90˚C). Moreover, the reaction conditions were selected carefully because hysteresis effects have been reported in previous studies. As indicated in Figure 4, the heat charging/discharging operation followed the reaction lines for the hydration and dehydration of CaCl2, as well as the experimental conditions (vapor pressure controlled by the evaporator or the condenser and inlet temperature of the heat-medium fluid tempering the reactor) used in this study (charging/discharging condition is denoted by white/black circles). During the discharging operation, the water vapor was transported from the evaporator to the reactor, where the exothermic reaction subsequently occurred. During the charging operation, the endothermic reaction charged the heat in the reactor and the released water vapor was transported to the condenser. Switching between the operations was implemented using the control valves on the vapor flow tubes. The flow rate of the heat-medium fluid for the reactor was 3.2 L/min for both operations.
Figure 4. Thermochemical reaction lines and experimental conditions (charging/discharging condition is denoted by white/black circles).
2.2. Calculation Method
COP was calculated as the heat enhancement mode evaluation parameter of CHP, based on the discharging and charging operation results. The following equations were used for the calculation; Qstorage means averaged volumetric power density for storage, Qrelease means averaged volumetric power density for discharging, Qoutput means averaged heat output, and Qinput means averaged heat input. Moreover, the change in amount of sensitive heat was considered assuming switching control between the discharging and charging operations. Additionally, the switching control time was out of consideration.
(5)
(6)
(7)
3. Results and Discussion
The discharging operation assuming the hot water output was demonstrated. Figure 5 shows the measurement result of the discharging operation at the reactor (90˚C) and evaporator (48˚C). The temperature of the heat-medium fluid flowing through the reactor rose from 90˚C to 98˚C.
Figure 6 shows time course of the averaged power density. The conversion ratio, shown in Figure 5, reached 0.8 after 600 s (350 W/L-reactor). The reaction rate is calculated from the temperature difference between the inlet and outlet of the heat exchange fluid. The heat of reaction is released to the environment in
Figure 5. Conversion ratio in the discharging operation at several temperatures of the reactor.
Figure 6. Averaged heat output in the discharging operation at several temperatures of the reactor.
addition to the heat transfer to the heat exchange fluid. Therefore, it is considered that the reaction rate has not reached 1. The change in the results caused by reactor temperature was small, so the influence of reactor temperature was confirmed to be small.
Figure 7 shows the experimental results of the charging operations. The conversion reached 0.8 at the reaction time of 600 s (350 W/L-reactor) at 175˚C, which is 2.9 times higher than the result with the reactor temperature of 170˚C. The condenser temperature also affected the heat charging behavior (Figure 8). The charging operation progressed at even 95˚C, so it was confirmed that the heat pump mode can be operated for a heat output of more than 90˚C. The charging rate showed a remarkable increase with decreasing condenser temperature.
Figure 7. Conversion ratio at several temperatures of the reactor.
Figure 8. Conversion ratio at several temperatures of the condenser (Trea = 175˚C).
The conversion ratio reached 0.8 after 600 s at the condenser temperatures of 85˚C and 90˚C. Condenser temperature at lower than 90˚C is required for the practical charging rate.
We then calculated the variations in Qoutput, Qinput, and COP with the time. The temperature conditions for the calculation follow: charging, 175˚C; discharging, 90˚C; evaporator, 48˚C; condenser, 90˚C.
Conversion ratio is calculated from Equation (3), and the heat of reaction is radiated outside the reactor in addition to the heat exchange fluid, so Conversion ratio has not reached 1.
As shown in Figure 9, Qoutput is higher than Qinput during operation, so the heat pump mode was confirmed. The instant heat output performance showed a peak value of more than Qoutput = 800 W/L-reactor, then Qoutput decreased through the remaining time. By contrast, COP increased with increasing time.
Figure 9. COP and averaged heat output in the heat pump system.
In actual use, it is assumed that the switching time of discharging and charging would be controlled to balance the reaction rate. Therefore, an output of 650 W/L-HEX and performance of COP 1.42 are shown at 600 s. At this time, the reaction is changed from discharging to charging.
The average output decreases and the COP increases after the arrival of the peak for the remaining amount of elapsed time. Therefore, COP has a trade-off relation with the average output. The change of COP with the average output after arrival of the peak is shown Figure 10. When the average output reaches the peak of 700 W/L-HEX, COP decreases suddenly. For performance enhancement, improvement of the heat and COP should be analyzed. It is necessary to consider the diffusion of water vapor and the promotion of heat transfer for designing the reactor. It is possible that the state of the packed bed changes due to repeated operations of hydration and dehydration reactions, which affects the performance of CHP. Such thermochemical storage systems show strong deactivation. Especially hydration reactions of alkaline earth chlorides lead to a fusion of the particles, which enhances pressure drop and makes the core of the particle inaccessible [16]. The unevenness of water vapor pressure in packed bed is considered. Water vapor does not easily reach deep inside the packed bed, and it is possible that the hydration rate of CaCl2 decreases. A research on a heat pump system using calcium sulfate as a heat storage material has been reported [13]. It is known that the diffusion rate of water vapor in the packed bed affects the performance of heat output. Therefore, the maximum value of heat output is tripled by providing a structure for promoting water vapor diffusion.
4. Conclusions
We evaluated output performance using a laboratory scale reactor with the condition of assuming a warm water output of around 90˚C. The output per volume of reactor and the COP were estimated from the result.
Figure 10. Change of COP with average output after the peak arrival.
When the periods of heat storage and heat release were switched at 600 s, an average output of 650 W/L-HEX and a COP of 1.42 were obtained. When the average output reaches the peak of 700 W/L-HEX, COP decreases suddenly. For performance enhancement, improvement of the heat and COP should be analyzed. This system is needed to be scaled up for practical use. Some problem is considered. In the future, we plan to design a device that promotes the diffusion of water vapor in the packed bed.