Analysis of a Large Grounding System and Subsequent Field Test Validation Using the Fall of Potential Method

HTML  Download Download as PDF (Size: 887KB)  PP. 1266-1272  
DOI: 10.4236/epe.2013.54B240    8,051 Downloads   10,320 Views  Citations

ABSTRACT

This paper examines various aspects of the design process and subsequent field test measurements of a large and complex substation grounding system. The study and measurements show that soil layering and lead interference can have a significant impact on the appropriate test location that yields the exact substation ground impedance. Applying a specific percentage rule such as the 61.8% rule for uniform soils to obtain the true ground impedance may lead to unacceptable errors for large grounding systems. This poses significant problems when attempting to validate a design based on raw test data that are interpreted using approximate methods to evaluate substation ground impedance, and determine ground potential rise (GPR), touch and step voltages. Advanced measurement methodologies and modern software packages were used to obtain and effectively analyze fall of potential test data, compute fault current distribution, and evaluate touch and step voltages for this large substation. Fault current distribution between the grounding system and other metallic paths were computed to determine the portion of fault current discharged in the grounding system. The performance of the grounding system, including its GPR and touch and step voltages, has been accurately computed and measured, taking into account the impedance of the steel material used of the ground conductors and circulating currents within the substation grounding system.

Share and Cite:

H. Huang, H. Liu, H. Luo, H. Du, Y. Xing, Y. Li, F. P. Dawalibi, H. Zhou and L. Fu, "Analysis of a Large Grounding System and Subsequent Field Test Validation Using the Fall of Potential Method," Energy and Power Engineering, Vol. 5 No. 4B, 2013, pp. 1266-1272. doi: 10.4236/epe.2013.54B240.

Cited by

[1] A New Lumped Parameter Modeling for Wind Farm Grounding Measurement Circuits Based on Clamp-on Ground Meters
Journal of Control …, 2024
[2] A systematic review on grounding impedance measurement in electrical installations
Salamanca - Electric Power Systems …, 2023
[3] A new approach for ground resistance measurements in onshore wind farms based on clamp-on meters and artificial neural network
Salamanca, AE Lazzaretti… - Electric Power Systems …, 2022
[4] Evaluation of a Methodology for Estimating the Symmetrical Ground Current in Substations: a Study Considering the Influence of Transmission Lines Guard Wire
… on Environment and …, 2022
[5] Application of the System Identification Method to Model the Transient Response of Grounding Plates
… on Lightning Protection (ICLP) and XVI …, 2021
[6] Substation Grounding Grid Diagnosis Applying Optimization Techniques Based on Measurements and Field Tests
2019
[7] Вдосконалення заземлювальних пристроїв електричних підстанцій для забезпечення безаварійної роботи вторинних кіл
2019
[8] Розрахунок заземлювальних пристроїв за допомогою програмного комплексу «LiGro»
2019
[9] Вдосконалення методів контролю та діагностики заземлювальних пристроїв діючих високовольтних енергооб'єктів України
2018
[10] Analysis of Grounding System in 150 kV Kudus Substation
2018
[11] Визначення електричних характеристик заземлювальних пристроїв електроустановок на основі повного моделювання об'ємних заземлювачів
2018
[12] Poboljšani metodi za merenje sigurnosnih karakteristika sistema uzemljenja u visokonaponskim postrojenjima
2016

Copyright © 2025 by authors and Scientific Research Publishing Inc.

Creative Commons License

This work and the related PDF file are licensed under a Creative Commons Attribution 4.0 International License.