Energy and Power Engineering

Volume 9, Issue 4 (April 2017)

ISSN Print: 1949-243X   ISSN Online: 1947-3818

Google-based Impact Factor: 0.66  Citations  

DC Emergency Power Control Strategy for AC/DC Multi-Channel Interconnected System

HTML  XML Download Download as PDF (Size: 1575KB)  PP. 735-747  
DOI: 10.4236/epe.2017.94B079    2,709 Downloads   3,603 Views  

ABSTRACT

Inter-regional transmission line fault often results in power flow transferring, tie-line overloading and system islanding. Traditional control methods such asgenerator tripping and load shedding are costly, and also have undesirable impacts on theloadside. In this paper, a new emergency power control strategy is proposed for multi-channel interconnected system by using the overload capacity of non-fault DC lines. First of all, the capacity of emergency power control can be acquired by critical transmission power of a certain tie-line for stability. Secondly, the shortest electric distance can be calculated by Dijkstra algorithm, and then the priority of emergency control of the DC lines can be obtained by the entropy weight method. When the inter-regional transmission power decreases and the effect of single DC line emergency control is poor, the multi-channel cooperative emergency control strategy is proposed to ensure the system stability. Simulation results verify the effectiveness of the method proposed.

Share and Cite:

Wang, Y. , Shao, D. , Zhang, Z. , Xu, Y. , Pan, X. and Sun, H. (2017) DC Emergency Power Control Strategy for AC/DC Multi-Channel Interconnected System. Energy and Power Engineering, 9, 735-747. doi: 10.4236/epe.2017.94B079.

Cited by

No relevant information.

Copyright © 2024 by authors and Scientific Research Publishing Inc.

Creative Commons License

This work and the related PDF file are licensed under a Creative Commons Attribution 4.0 International License.