Paper Menu >>
Journal Menu >>
![]() Journal of Environmental Protection, 2009, 1, 59-67 Published Online November 2009 (http://www.SciRP.org/journal/jep/). Copyright © 2009 SciRes. JEP 1 Impact of Reactive Power in Power Evacuation from Wind Turbines Asish RANJAN1, S. Prabhakar KARTHIKEYAN1, Ankur AHUJA1, K. PALANISAMY1, I. Jacob RAGLEND2, D. P. KOTHARI3 1School of Electrical Sciences, Vellore In stitute of Technology, Vellore, India-632014; 2Christian College of Engineering and Tech- nology, Ottanchatiram, Dindugal District. India-632014; 3Vellore Institute of Technology University, Vellore, India-632014. Abstract Application of Distributed Generation (DG) to supply the demands of a diverse customer base plays a vital role in the renewable energy environment. Various DG technologies are being integrated into power systems to provide alternatives to energy sources and to improve reliability of the system. Power Evacuation from these remotely located DG’s remains a major concern for the power utilities these days. The main cause of concern regarding evacuation is consumption of reactive power for excitation by Induction Generators (IG) used in wind power production which affects the power system in variety of ways. This paper deals with the issues related to reactive power consumption by Induction generators during power evacuation. Induction generator based wind turbine model using MATLAB/SIMULINK is simulated and its impact on the grid is observed. The simulated results are analyzed and validated with the real time results for the system consid- ered. A wind farm is also modeled and simulations are carried out to study the various impacts it has on the grid & nearby wind turbines during Islanding and system event especially on 3-Phase to ground fault. Keywords: Distributed Generation (DG), Grid, Wind Turbines, Induction Generator, Islanding, Power Evacuation, Point of Common Connection 3 Phase to Ground Fault 1. Introduction Wind is one of the most important resources found in nature’s bounty totally free of cost and without any hazardous effects. Perhaps that is why, in this hour of energy crisis,the entire human race has diverted its attention to wind energy as a suitable alternative to the conventional sources of energy we have been using for more than a century. Having an insight into the statistics concerning installed wind power capacity,we see that the total capacity as of today is 93,849MW (2008). India stands fourth in wind power commissioning with an installed capacity of 7844.5MW (2008). But Germany with a capacity of 22,247MW (2008) shows that the distance to be covered is still huge. Of course, it instills a hope that the future will be bright with no reliance on conventional sources of energy and wind energy forming a large chunk of the installed capacity. There are two types of utility-scale wind turbines, fixed-and variable-speed. Fixed-speed wind turbines operate at a near constant rotor speed at all times and are directly connected to the power grid [1]. Fixed speed wind turbine which is used here for analysis operates within a very small range (around 5% of the nominal value) and in general they use a fixed shunt capacitor to provide reactive power compensation [2]. 1.1. Islanding A phenomenon which generally occurs in a network with Wind Generation in which a portion of the distribution network becomes Electrically Isolated from utility grid due to transmission system events & after disconnection, wind generator maintains supp ly to local loads. Islanding can be categorized as Intentional Island and Unintentional Island. Islanding is a condition in which local Distribution Generation systems continue to supply stable real power and reactive power to the local loads at a sustained voltage ![]() 60 R. ASISH ET AL. and frequency while the main Energy system is de-ener- gized. An islanding condition creates a safety hazard and may cause damage to power generation and power supply facilities as a result of unsynchronized re-closure [3]. In general, after loss of the main source, the DG has to take charge of the remaining network and the connected loads; therefore, the loading condition of the DG is suddenly changed after islanding. Since the distribution networks generally include single-phase loads, it will be highly pos- sible that the islanding changes the load balance of DG [4]. 1.2. Intentional Island Planned islanding is often called Intentional Islanding. This condition arises when a portion of the network is separated from the rest of the network for the sake of system reliability & maintaining the safety of the network . Utility personnel monitor the islanded system continu- ously & it poses no problem for the utility. During the occurrence of a system outage, when sev- eral groups of generators can go out of-step with each other, it may be desirable to have selected islands where there is a minimal mismatch between load and generation. Switching operations carried out to split the system into such self-sufficient regions is called intentional islanding. 1.3. Unintentional Island Sudden and unpredicted islanding is termed as uninten- tional islanding which mainly results due to th e failure of anti-islanding techniques resulting in electrical isolation of an energized portion [5]. The energized portion will continue to su pply power to the loads present in the island affecting the safety concerns for the utility personnel. A section of the grid having balanced load and gen- eration may become isolated from the rest of the grid by a sudden opening of a switch or a circuit breaker that causes the disconnection of the feeder from the grid. A common form of disconnection would typically arise from a momentary ground fault on the feeder, which is detected by the feeder ground relay and results in tripping of the feeder circuit breaker. Such an event is described in Figure 1. The single line to ground fault shown in the Figure1 is assumed to be transient in na- ture [6]. This fault could cause operation of utility breaker shown as a disconnection point suggested by the given Figure 1. However, the transient fault may be undetectable by the DG and cause to exist after opening of the utility breaker. In this scenario, an unintentional island is formed after opening of the utility breaker. After dis- connection from the grid, this island may be initially deficient in active and reactive power. The deficiency of active power is balanced by the release of kinetic energy from the rotating machinery connected to the system, and hence reduction in system frequency [6]. The deficiency of reactive power is mainly balanced by the export of reactive power from the embedded synchronous generator .An islanding event, such as described in this section, can be conveniently illus- trated by a frequency and voltage versus time graph of Figure 2. 1.4. Implications of Inadvertent Islanding Inadvertent islanding presents a number of safety, com- mercial, power quality, and system integrity p roblems [7]. In summary, the major issues are: 1) Line worker safety can be threatened by DG sources feeding a system after primary sources have been opened and tagged out. 2) Public safety can be compromised as the utility does not have the capab ility of de-energizing downed lines. 3) The voltage and frequency provided to other customers connected to the island are out of the utility’s control, yet the utility remains responsible to those customers. 4) Protection systems on the island are likely to be unco- ordinated , du e to the dr astic ch ang e in short circuit cu r- rent availability. 5) The islanded system may be inadequately grounded by the DG interconnection. Figure 1. Ground fault disconnection. Copyright © 2009 SciRes. JEP ![]() R. ASISH ET AL. 61 Figure 2. Voltage and frequency response 6) Utility breakers or circuit reclosers are likely to re- connect the island to the greater utility system when out of phase. 2. System Configuration The parameters used for the simulation of the above model of an Induction Generator based wind turbine are as follows: 2.1. Induction Generator A 3-phase squirrel cage induction generator with a nomi- nal power of 843KVA, 690V (φ-φ), 50 HZ is used for the above system wi t h the parameters shown in Table 1. 2.2. Three Phase Transformer A Yg/ ∆ (D1) configuration of three phase (2-winding) transformer is used with a nominal power of 1MVA with following primary/Secondary Windings given in Table 2. Parameters used for the simulation of three phase PI sec- tion Line was given in Table 3. Table 1. Induction generator parame ter s Parameter Unit Stator Resistance R1 0.0045 Ω Stator Leakage Reactance X1 0.0513 Ω Magnetizing Reactance Xh 2.2633 Ω Rotor Reactance(referred to Stator) X’2 0.066 Ω Rotor Resistance( referred to Stator) R’2 0.004 Ω Magnetizing Resistance Rfe 83.3 Ω 2.3. Grid A three-phase source with internal R-L impedance is used to implement a grid which is connected to the wind Generator through a T-Line & Transformer. The three phase Short-circuit Level at base voltage of 33KV is 25MVA with X/R ratio of 10. 2.4. Load A 3-Phase resistive load of 675KW is used which is con- nected at the terminals of wind turb ine. Simple wind farm based on fixed speed wind turbines is connected to a grid through a T-Line at Point of Common Connection (PCC) Table 2. WG Transformer parameters Parameters Primary Winding Secondary Winding Voltage (φ-φ) rms(KV)33 0.690 Resistance(R) pu 0.0125 0.039 Inductance(L) p u 0.0125 0.039 Table 3 Parameters for PI section Transmission line Parameters Positive Sequence Zero Sequence Resistance(Ω/Km) 0.1153 0.413 Inductance(mH/Km) 1.05 3.32 Capacitance(μF/Km) 11.33 5.01 Figure 3. System configuration in SIM ULINK. Co pyright © 2009 SciRes. JEP ![]() 62 R. ASISH ET AL. The second module of the paper deals with the Imple- mentation of a Wind Farm & its Impact on Grid during Islanding which can be categorized as: 1) Wind Farm Configuration in SIMULINK. 2) Impact on Grid during Disconnection of a Wind Generator. 2.5. Wind Farm Configuration A Wind Farm with three Identical Wind Turbines con- nected together to form a Wind farm of capacity 2.25MW is shown in the Figure 5. In implementing a wind farm connected to a grid through a PCC needs a separate step-up Transformer at the PCC which is finally connected to the grid via Pi section T-Line. The difference between a single wind Turbine connected to a grid & a wind farm connected to grid can be seen by an additional Transformer’s & Individual short transmission lines connecting each Generator to PCC with their parameters mentioned below. 2.6. Transformer With nominal power 10MVA a 33/66KV transformer 2.7 T-Line with same parameters specified before. Short transmission lines connecting Individual Wind generators are of length 1 Km each with same parameters specified before. The Islanding of a Wind turbine model is shown in Figure 6 using SIMULINK. The Impact of Disconnec- tion of one of WG from the rest of the network is im- plemented here by Inserting a 3-phase breaker in series with the same WG & PCC in which switching of all the three phases from closed to open condition takes place after 1.5 Sec of operation of WG. The parameters for the Breaker are Transition Time: 1.5 Sec, Breaker Resistance: 0.001 Ω, Snubber Resis- tance: 0.000001 Ω, Snubber Capacitance: ∞. Figure 7 is implemented in SIMULINK to Simulate Unintentional Islanding Condition. 2.7. Induction Generator A 3-phase squirrel cage induction generator with a nominal power of 1.66MVA, 575V (φ-φ), 60 HZ is used for the above system with the parameters shown in Table 4. Q P Tx Line T r GRID LOAD PCC Figure 4. Outline of grid connected wind farm. Figure 5. Wind farm connected to grid using SIMULINK. Copyright © 2009 SciRes. JEP ![]() R. ASISH ET AL. 63 Figure 6. Islanding of a Simulated Wind turbine model. Figure 7. Netw ork layout used for Simulation [8]. Table 4. Parameters for Induction Gener ator [8]. Parameter Unit Stator Resistance R1 0.004843 pu Stator Leakage inductance L1 0.1248 pu Magnetizing Inductance Lm 6.7 pu Rotor inductance ref to Stator L’2 0.1791 pu Rotor Resistance ref to Stator R’2 0.004347 pu Table 5. Three Phase Transformer parameters [8]. 3-Phase 4MVA transformer (Yg/Yn) 47MVA grid side trans- former Yg/∆(D1) Parameters Primary Winding Secondary Winding Primary Winding Secondary Winding Voltage (φ-φ) rms(KV) 33 0.575 132 33 Resistance(R) pu 0.025/30 0.025/30 0.08/30 0.08/30 Inductance(L) pu 0.025 0.025 0.08 0.08 A grounding Tr ansformer is used to create a ground ing point at the secondary side (∆) of grid 47MVA trans- former with Xo=4.7 Ω [8]. 2.8. Grid A three-phase ideal voltage source along with a 3-phase mutual inductance block is used a grid with a capacity of 2500MVA&Xo/X1=3 [8]. 3. Case Studies and Results 3.1. Normal Condition without any C ompe nsat ion For a Wind Farm of 2.25 MW under normal working condition, following results were obtained. The waveform of P & Q at the Wind Generator termi- nals is shown in Figure 9. The waveform of P & Q at the Grid terminals are shown in Figure 10.The waveform of V, I, P & Q at the load terminals are shown in Figure 11.The loading conditions without any reactive power compensation are Load= (750+360j)*3, C1=C2=C3=0. It is found that the requirement of reactive power by Induction generators witho ut compensation is fulfilled by the grid which results in large deviation from the standard oltage values. v Grid supply point and sub- station 132 kV / 2500 MVA 12345 132 / 33 kV L1L2 L3 L4 L5 678 3×33 kV/575V WTIG-3 WTIG-2 WTIG-1 250 kVAR 1.5 MW3 MW4.5 MW 500 kVAR 1000 kVAR Co pyright © 2009 SciRes. JEP ![]() 64 R. ASISH ET AL. Figure 8. Simulated Model for Unw a nte d Islanding. 3.2. Islanding Condition Following results were obtained under Islanding condi- tion. The waveform of P & Q at the Wind Generator ter- minals are shown in Figure 12. The Frequency Response at the Wind Generator Terminal is shown in Figure 13. The waveform of V, I, P & Q at the Grid terminal are shown in Figure 14. The waveform of V, I, P & Q at the Load terminal are shown in Figure 15. 3.3. Unintentional Islanding Condition Following results were obtained under Unintentional Islanding condition where Islanding can be detected by conventional method. For PG=1.5MW , QG=-750 KVAR, PL=1.2 MW, QL=20 KVAR, QC=250KVAR. The waveform of V, I, P & Q at islanded Wind Gen- erator terminals are shown in Figure 16. Table No. 6 shows the simulated results of the Voltage at Generator Terminal for the clearing time. And Table 7 shows the IEEE Standards for Interconnection system response to abnormal voltages. From the waveform as df/dt=1.19 HZ/Sec, ∆f =2.38HZ, f’ = f-∆f = 57.62Hz. It is found that Islanding can be detected by the Con- ventional methods based on local parameters. Thereafter Islanding can be prevented in accordance with IEEE 1547 standards. Table 8 shows the IEEE Standards for Interconnection system response to ab normal frequencies. The Impact of 3-phase to ground fault is analyzed by considering the Wind Farm Capacity of 2.25MW and 4.5MW. Table 6. Voltages at WG terminal (PL=1.2MW). 4 SEC 6 SEC 0.961 pu 0.46 pu Table 7. IEEE 1547 standard (for voltage). Voltage Range (% of Base Voltage) Clearing Time 50≤V≤88 2 Sec Table 8. IEEE 1547 standard (for frequency). WG size Frequency range Clearing Time >30KW <(59.8-57) Adjustable 0.16s to 0.3s Copyright © 2009 SciRes. JEP ![]() R. ASISH ET AL. 65 Figure 9. P & Q waveform at WG terminals. Figure 10. P & Q waveform at Grid terminals. Figure 11. V, I, P & Q waveform at Load End. Figure 12. P & Q waveform at WG terminal during disconnection of one WG. Figure 13. Frequency Response at WG Terminal. Co pyright © 2009 SciRes. JEP ![]() 66 R. ASISH ET AL. Figure 14. V, I, P & Q waveform at Grid End. Figure 15. V, I, P & Q waveform at Load terminal. Figure 16. V, I, P, Q waveform at islanded WG End (PL=1.2 MW). Figure 17. Waveform of V, I, P, Q at Grid terminal during 3 phase fault at t= 1 sec. Figure 18. Waveform of P, Q at Grid terminals du ring 3 phas e fault at t=1sec (Wind Farm Capacity= 4.5MW, Grid =25MVA). Copyright © 2009 SciRes. JEP ![]() R. ASISH ET AL. 67 Copyright © 2009 SciRes. JEP Figure 19. Waveform of P, Q at Grid terminals during 3 ph as e fault at t=1sec (Wind Farm Capacity=4.5MW, Grid=50MVA). 3.4. Wind Farm Capacity of 2.25MW The oscillation in frequency is not acceptable where deviation is more than 5 Hz. Maximum oscillation is observed when the wind farm capacity is observed when the wind farm capacity is 4.5 MW. In Figure 17, response of 3 phase fault at grid terminals is shown when the capacity of wind farm is 2.25 MW & that of Grid is 25MVA. The fault is initiated at t= 1sec & gets self cleared at t=1.1sec. 5. References 3.5. Wind Farm Capacity of 4.5MW [1] S. Santoso, H. T. Le, “Fundamental time-domain wind turbine models for wind power studies,” Renewable En- ergy 32, pp. 2436-2452, 2007. When the capacity of the grid is doubled to 50 MVA, following res ponse is obtained at grid term inal s. 4. Conclusions [2] K. C. Divya and P. S. N. Rao, “Models for wind turbine generating systems and their application in load flow studies,” Electric Power Systems Research 76, pp. 844-856, 2006. This paper demonstrates the impact of islanding during- power evacuation from wind turbin es. It is found that the problems associated with power evacuation from wind farms entirely depends on the network topology. A Smaller generating system (i.e. for 2.25MW) can sustain and function stably with a grid capacity of 25MVA. To keep the system in stable, the grid capacity has to be in- creased doubly (i.e. 50 MVA). It is found that Index based methods for anti-islanding doesn’t ensure preven- tion from islanding as Index threshold could change due to change in system load, generation and configuration. The Voltage based Anti-Islanding technique fails to de- tect Islanding if the transfer of reactive power from grid to wind farm is kept minimum. The Islanding of single wind turbine has very little impact on nearby wind tur- bines and grid if it is detected in the given time. [3] C. Diduch, J. Yin, and L. C. Chang, “Recent developments in islanding detection for distributed power generation,” Large Engineering Systems Conference, pp. 124-128, 20 04. [4] S. I. Jang and K. H. Kim, “An islanding detection method for distributed generations using voltage unbalance and to- tal harmonic distortion of current,” IEEE transactions on power delivery, Vol. 19, No. 2, April 2004. [5] IEEE Standard 15477M, “Standard for interconnecting distributed resources with electric power systems”, June 2003. [6] N. Farhan, A. Rajesh, and V Y. Mohammad, “Uninten- tional islanding and comparison of prevention tech- niques,” Proceedings of 37th Annual North American Conference, pp. 90-96, 2005. The impact of three phase fault power evacuation from wind turbines is found that the problems associated with power evacuation from wind farms entirely depends on the network topology. [7] R. A. Walling and N. W. Miller “Distributed generation islanding-implications on power system dynamic per- formance,” Proceedings of the IEEE/PES, Summer Power Meeting, Chicago, July 2002. When the capacity of the Wind farm is doubled, system events results in unstable operation of the network. Instability can be seen from the changed operation condition after the fault is cleared at 100ms. The impact is minimised by increasing the capacity of the grid to 50 MVA. [8] S. Panda and N. P. Padhy, “Investigating the impact of wind speed on active and reactive power penetration to the distribution network,” International Journal of Electri- cal Systems Science and Engineering, Vol. 1, No. 1, ISSN 1307-8917, 2008. |