A Protection Method of VSC-HVDC Cables Based on Generalized S-Transform ()
1. Introduction
More and more VSC-HVDC projects are using cables as transmission lines. Due to the small damping of VSC-HVDC System, DC cable fault will cause serious over-current in a short time, which will lead to serious faults on transmission cables and the converter. In addition, VSC-HVDC system has some problems, such as fault identification, self-healing and so on [1] [2] [3]. Therefore, it is significant to study the fault characteristics of VSC-HVDC cables and realize the protection of VSC-HVDC System by analyzing the fault characteristics. The S transform was proposed in [4] and [5] by Stockwell. In [6] and [7], the feature signal is extracted by S transform of the fault signal. Then, the fault identification index is built. We use the value domain of fault index to determine the fault type. Reference [8] proposed the research of fast protection for UHVDC transmission line based on S-transform. The voltage and current components after fault are transformed by S-transform, and the polarity of voltage and current components at both ends of the line is judged by the phase difference of the whole frequency band after S-transform, so as to distinguish between internal and external faults. A protection method for HVDC transmission line based on S-transform is represented in [9]. Reference [10] and [11] use S-transform to locate fault cables through fault current. A serious drawback with S-transform in the above literature is that the time-frequency resolution of S-transform is not precise enough. In this paper, the fault current is transformed by Generalized S-transform, which has a better time-frequency resolution than S-transform. In this paper, the basic theory of Generalized S-transform and Phase-Mode transformation are introduced in Section 2. Section 3 represents the simulation model of two-terminal VSC-HVDC. The protection method is described in Section 4. Experimental results are shown in Section 5 to verify the proposed method.
2. Basic Theory
2.1. Generalized S-Transform
The S transform is a time-frequency analysis method, which derived from continuous wavelet transform and short-time Fourier transform. The S transform of a signal
is expressed as:
(1)
where:
is Gaussian window function
with a time-shift factor τ and a frequency f. The S transform of a discrete signal
is expressed as:
. (2)
. (3)
where m = 0, 1, 2, …, N − 1, N is the number of sampling points, and T is the sampling time interval. Based on the S transform, the Generalized S-transform can be obtained and described as follow:
(4)
where:
. In Equation (4), α and β are regulator,
positive numbers. By adjusting parameters of α or β, superior time-frequency characteristic of the signal is obtained.
2.2. Phase-Mode Transformation
The cross section of bipolar cable is shown in Figure 1. From inside to outside, there are three layers: conductor layer, sheath layer and armor layer. The voltage and current parameters in the bipolar cable are coupled with each other. It is obliged to decouple the parameters.
Reference [9] and [10], the decoupling method for the bipolar DC line was represented, which is described as follows: The sketch map of DC cable is shown in Figure 2. The output terminal of rectifier and inverter station are marked as 1
Figure 1. The cross section of biploar cable.
and 2, respectively. Taking terminal 1 as an example, up1c, up1s and up1a represents the DC voltage of conductor layer, sheath layer and armor layer of the positive cable at terminal 1 respectively. un1c, un1s, un1a are the DC voltage of conductor layer, sheath layer and armor layer of the negative cable at terminal 1 respectively. The same applies to terminal 2.
Define R, L, G and C as the matrices of the resistance, inductance, conductance and capacitance per meter of the DC cable respectively, and the wave equations with mutual inductance can be represented as follows:
(5)
,
. The key to realizing the decoupling is to transform R, L, G and C to diagonal matrices. According to this principle, the voltage phase mode transform matrix can be derived and represented as follows:
(6)
where 0 and I are the 2-dimensional zero matrix and unit matrix respectively, while k is the decoupling transform matrix expressed as
(7)
Introduce Q = P−T as the current phase mode transform matrix, and Equation (3) can be transformed to
(8)
where I1m is expressed as:
(9)
According to [9] and the reference direction of currents in Figure 2, the 6-th mode current is employed because its attenuation constant is lowest and the propagation velocity is close to traveling wave.
3. Simulation Model
Taking a two-terminal VSC-HVDC as an example, we build its system simulation model and some typical faults are carried out in PSCAD/EMTDC. The fault model is shown in Figure 3. The length between rectifier station and inverter station is 200 (km), p1, p2, n1, n2 are relay protection devices. Fault F1 is at the middle point of the positive cable. F2 is the bipolar short-circuit fault. F3 and F4 are fault in the AC system, respectively. In this paper, F1 and F2 are internal faults, F3 and F4 are external faults.
The parameters of rectifier station and inverter station are shown in Table 1. The DC voltage in this paper is 350 (kV).
4. Protection Method
The 6-th mode current is employed to establish criteria. The Generalized S-transform result matrix of 6-th mode current is marked as
. When a fault occurs, there are abundant frequency components in the DC cable. The summation of the magnitude of high frequency (5 kHz - 10 kHz) at the time kT can be calculated as:
(10)
where
,
.The criteria that the first sudden change time of Sum is the time of fault based on numerous experiments. When the VSC-HVDC operates normally, Sum is 0. So the criteria of when the fault occurs can be built as follows: when Sum > Sumh, it indicates that there is a fault. Sumh is the threshold which is obtained in this case: the fault resistance is set to 500 (Ω) and during the remote fault. In this paper, Sumh is 0.5. The disturbance caused by noise can also cause high frequency in the cable. To estimate the disturbance, the zero frequency of the
is employed to establish criteria, which can be obtained as follows:
(11)
The
is the difference of 6-th mode result after Generalized S-transform when VSC-HVDC operates normally and when there is a fault or disturbance.
Based on mounts of experiments, the criteria can be built as following: when
, it indicates there is a fault, otherwise, it is disturbance. Where h is threshold which should be smaller than
.
is the difference of 6-th mode current after Generalized S-transform when VSC-HVDC operates normally and when there is a remote fault with the largest resistance. In this paper, k is 0.8.
It is necessary to identify the external fault from internal fault because the external fault can also cause the sudden change of sum. Take the monopole to earth fault as an example. The simplified diagram of the system after fault F1 is shown in Figure 4. Rf is the fault resistance and ∆uf is the additional voltage source at the fault point. The voltage between the fault point and the ground is ∆u. Zp12 is the equivalent impedance of cable12. Zs1 and Zs2 are the equivalent impedance of AC sides, respectively. Measured by the protection devices p1 and p2, the fault current component is named as ∆ip1 and ∆ip2. The reference directions of the DC currents are represented by the arrows displayed in the figure. Seen from Figure 4, the relation of ∆u, ∆ip1, ∆ip2 can be expressed in Equation (12). From Equation (12), the polarities ∆ip1 and ∆ip2 are opposite.
(12)
The simplified diagram of the system after an external fault F3 at the rectifier side is shown in Figure 5. Zs1f is the equivalent impedance from the fault point to DC-link capacitor. The relation of ∆u, ∆ip1, ∆ip2 can be expressed in Equation (13). Obviously, ∆ip1 and ∆ip2 have the same polarity.
(13)
The flowchart of the protection method is expressed as follows: (Figure 6)
Figure 4. The simplified diagram after fault F1.
Figure 5. The simplified diagram after fault F3.
Figure 6. The flowchart of the protection method.
5. Experiment Results
5.1. Internal Faults
Internal faults are composed of monopole to earth fault and bipolar short-circuit fault. Numerous internal faults are simulated to verify the reliability of the proposed protection method, which are shown in Table 2. This section takes the simulation results of monopole to earth fault with the fault resistance of 100 (Ω) at F1 as an example, which is shown in Figure 7. As shown in (a), (b), IP1, IN1, IP2, IN2 are the currents after fault measured at p1, n1, p2, n2, respectively. The 6-th mode current I1 and I2 are calculated from them. Sum1 and Sum2 are shown in (c). at 0.5s, Sum1 and Sum2 are both reach the sudden change point and the peak values are larger than Sumh. ∆GS01 and ∆GS02 are both larger than h, which are shown in (d). As shown in (e), the polarities of ∆i1 and ∆i2 are opposite, which indicates that there is an internal fault in the DC cable.
5.2. External Faults
The simulation results of external faults are shown in Table 3.
Figure 7. The simulation results for fault at F1.
Table 2. Simulation results for internal faults.
Table 3. Simulation results for external faults.
6. Conclusion
This paper proposed a novel protection method for VSC-HVDC based on Generalized S-transform. Firstly, using Generalized S-transform to extract frequency component of fault current and employing mutation point of high frequency to determine the fault time. Secondly, eliminating disturbances using the zero-frequency component of fault current. Finally, the polarity of sudden change currents in the two terminals is employed to discriminate the internal and external faults. Simulations in PSCAD/EMTDC and MATLAB show the accuracy and effectiveness of the proposed method.