Study on the Calculation of 35 kV Parallel Gap Arcing Time Considering the Influence of Wind Load

Abstract

Wind load is the important factor influencing arc-extinguishing of arc. Establishing arc chain motion model of 35 kV parallel gap under wind load condition, the electromagnetic force, air resistance and wind force of a single arc element are analyzed by using the chain arc model. The arc motion parameters were solved. The arc anti-resistance and arc resistance are calculated; the criterion of arc extinguishing is defined; the arc burning time is calculated, and the arc burning time is obtained. Through the calculation of arc ignition time, it can be seen that the magnitude of wind load affects the arc free time. When the wind load increases, the arc ignition time will be shortened.

Share and Cite:

Huang, C.J., Wu, D. and Ji, Z.L. (2021) Study on the Calculation of 35 kV Parallel Gap Arcing Time Considering the Influence of Wind Load. Open Access Library Journal, 8, 1-8. doi: 10.4236/oalib.1107614.

1. Introduction

Modern lightning protection measures are divided into “blocking” and “de-blocking” [1] [2] [3] [4] [5]. The core idea of the “blocking” type of lightning protection is to improve the lightning resistance of the line as much as possible to reduce the lightning trip rate. This approach is suitable in the case of few power points and a weak grid, but the “blocking” type of lightning flashover means that it requires huge investments and is technically difficult to implement [6]. The core idea of the “de-escalation” type of lightning protection is to allow a small increase in the lightning trip rate of the line and to divert the lightning flow to protect insulators from damage and avoid lightning strikes [7] - [15].

The most typical “channeling” method is to install parallel gaps next to insulators. Japan, Germany, France and other countries have been studying the use of parallel discharge gaps on overhead transmission lines since the 1960s, and have accumulated a wealth of technical data and operational experience, and now almost all insulator strings are equipped with discharge gaps of different shapes [16] [17] [18].

In this paper, we propose a method to calculate the arc ignition time of 35 kV parallel gaps under the influence of wind load, draw the corresponding conclusions by calculating the arc ignition time and compare the difference of arc ignition time considering the influence of wind load. Therefore, the research in this paper can effectively reduce the accident rate of lightning strikes and ensure the reliable operation of power lines.

2. Working Principle of 35 kV Parallel Gap Device

The structure schematic of 35 kV parallel gap device is shown in Figure 1. The parallel gap device is mainly a pair of metal electrodes connected in parallel at both ends of the insulator string to form a protection gap. Under the action of electrodynamic force and wind load, the arc will move toward the electrode end and burn at the electrode end of the parallel gap, so that the arc length will be elongated and the arc energy will be decayed, then the arc will be extinguished, effectively protecting the insulator from arc burns.

3. Parallel Gap Arc Burning Time Calculation Method

3.1. Arc Element Modeling

An arc chain model is established as shown in Figure 2.

For any current element, the force analysis is shown in the following Figure 3.

F f i + F d i + F z i = 0 (1)

Figure 1. A schematic diagram of 35 kV parallel gap device.

Figure 2. Chain arc model.

Figure 3. Force analysis of arbitrary arc element.

where, F f i , F d i , F z i are the wind force, magnetic field force and air resistance respectively for the ith arc element.

The magnetic field force equation:

F d i = B i I i l i (2)

Wind force equation:

F f i = ρ v f 2 C s S i 2 (3)

F z i = C R ρ v i 2 r i l i (4)

where, B i is the magnetic induction intensity of the ith arc element; l i is the arc length of the ith arc element; v f is the wind speed; v i is the velocity of the ith arc element; S i is the area of the side cross section of the ith arc element; C s is the shape factor; C R is a constant; r i is the radius of the ith arc element.

The joint system of Equations (1)-(4) yields:

v i = F d i + F f i C R ρ r i l i (5)

3.2. Arc Resistivity

The arc resistivity expression is:

ρ = m e v e i n e e 2 = m e e 2 ln Λ 32 π ε 0 2 T e 3 / 2 (6)

m e : electron mass, taken as 9.1 × 1031 kg.

e : electron charged amount is 1.76 × 1019 C.

ε 0 : vacuum medium constant 8.85 × 1012 F/m.

T e : electron temperature.

T e = n e V = I S V (7)

where, n e is the electron density, V is the volume of the arc column, and S is the cross-sectional area of the arc column.

ln Λ ln ( T 3 / 2 e 2 n 1 / 2 ) (8)

InΛ: Coulomb logarithm, where n is the number density of particles in the arc and T is the arc temperature. In general, InΛ take the value range of 10 - 20.

3.3. The Solution of Arc Resistance

The moving state of the current element at a certain instant under the wind load is shown in Figure 4 below.

Then the arc resistance is:

R = R 1 + R 2 + R 3 + R 4 + R 5 (9)

As shown above, let the arc resistance R1, R2, R3, R4, R5 corresponding to the arc length of l 1 , l 2 , l 3 , l 4 , l 5 , respectively.

Figure 5 shows the overlapping cross section of the first arc element and the second arc element.

Figure 4. Arc element motion diagram at some time.

Figure 5. A cross section of arc element and second arc elements.

h = r 1 sin β (10)

d = r 1 cos β (11)

where r 1 is the radius of the first current element; β is the angle between O1A and O1O2.

S Δ O 1 A B = 1 2 d h = 1 2 r 1 2 sin β cos β (12)

S O 1 A C = r 1 2 β (13)

Therefore, the overlapping area S is:

S = 4 × ( S O 1 A C S Δ O 1 A B ) = 4 × ( r 1 2 β 1 2 r 1 2 sin β cos β ) (14)

d ( t ) = 1 2 v 2 t (15)

where, v 2 is the velocity of motion of the second arc element and t is the time.

sin β = h r 1 = r 1 2 d ( t ) 2 r 1 (16)

cos β = d r 1 = v 2 t 2 r 1 (17)

Then the expression for the overlapping area S can be converted to:

S = r 1 2 ( 4 × arccos v 2 t 2 r 1 v 2 t r 1 2 d ( t ) 2 r 1 2 ) (18)

D = 0.26 I (19)

r 1 = 0.13 I (20)

where D is the diameter of the arc element.

According to the resistance formula, the simplification gives:

R 1 = ρ l 1 s 1 = l 1 m e e 2 I n Λ 0.5408 π I π ε 0 2 T e 3 / 2 (21)

R 2 = ρ l 2 s 2 = m e e 2 I n Λ 32 π ε 0 2 T e 3 / 2 B (22)

Table 1. Arc ignition times at different airflow parameters.

R 3 = ρ l 3 s 3 = l 3 m e e 2 I n Λ 0.5408 π I π ε 0 2 T e 3 / 2 (23)

R 4 = ρ l 4 s 4 = l 4 m e e 2 I n Λ 0.5408 π I π ε 0 2 T e 3 / 2 (24)

R 5 = ρ l 5 s 5 = l 5 m e e 2 I n Λ 0.5408 π I π ε 0 2 T e 3 / 2 (25)

R = R 1 + R 2 + R 3 + R 4 + R 5 = m e e 2 I n Λ 32 π ε 0 2 T e 3 / 2 ( l 1 + l 3 + l 4 + l 5 0.0169 π I + B ) (26)

Formula analysis:

Arc resistance and electron temperature is inversely proportional to the 3/2 times. As the arc temperature decreases, the arc resistance increases; finally, the arc tends to be extinguished.

3.4. Arc Extinguishing Criterion

Arc resistance gradually grows to infinity, the arc gradually extinguished. In the arc current after the zero number of ms, all meet the condition dR/dt > 0, the arc is judged to be extinguished.

3.5. Calculation Results

Through the above calculation method can be obtained under different parameters of the arc burning time, as shown in Table 1.

4. Conclusions

1) Through the establishment of the arc model and theoretical calculations, it can be derived that the wind load affects the arc burning time change, when the wind speed increases, the same current value case, the shorter the arc burning time.

2) In the following situations of the wind load speed of 300 m/s, the arc current of 0.5 kA, the wind load and the vertical direction of the angle of 60˚, the arc burning time of 2.69 ms.

3) According to the calculation results, it can be concluded that the arc in the wind load, the arc temperature decreases; and then the arc resistance increases, the arc extinguishing speed accelerates, the arc ignition time decreases.

Acknowledgements

This research was supported by the Doctoral Research Initiation Fund of Guilin University of Technology (GUTQDJJ2018068) and 2020 Guangxi University Middle-Aged and Young Teachers’ Basic Research Ability Improvement Project (2020KY06024).

Conflicts of Interest

The authors declare no conflicts of interest.

References

[1] Luo, Z.H., Chen, M., Chen, W.J., et al. (2002) Study on Shunt Gap Lightning Protection for 110kV and 220kV Composite Insulators. Power System Technology, 26, 41-47.
[2] Zhang, W., He, J.L. and Gao, Y.M. (2002) Overvoltage Protection and Insulation Fit in Power Systems. Tsinghua University Press, Beijing.
[3] He, J.L., Zeng, R. and Chen, S.M. (2009) Lightning Protection Study of Transmission Line, Part III: Protection Measures. High Voltage Engineering, 35, 2917-2923.
[4] Sima, W.X., Zhang, Z., Yang, Q.Y., Yuan, T., Ye, X., Liao, Y., et al. (2012) Experimental Research on Power Frequency Arc Movement Process of 110kV Composite Insulators in Rod Shape Parallel Gap Lightning Protection Device. Proceedings of the CSEE, 32, 114-121, 226.
[5] Yan, X.L., Chen, W.J., Wang, C.Y., et al. (2009) Computation of Secondary Arc Self-Extinction Behavior with the Influence of Wind. Proceedings of the CSEE, 29, 1-6.
[6] Yan, X.L. (2009) Research on the Self-Extinguishing Characteristics of Single-Phase Grounding Potential Arc of AC Transmission Lines. China Electric Power Research Institute, Beijing.
[7] Chen, M., Wu, B.H. and Luo, Z.H. (2001) On “Scatter” Type Lightning Protection Scheme for HV Overhead Power Transmission Lines. Guangdong Electric Power, No. 4, 36-37+58.
[8] Yang, Q.F. (2009) Measures of Strengthening Lightning Protection for High Voltage Overhead Line. Metallurgical Power, No. 4, 12-15.
[9] Ge, D., Shen, H., He, Z., et al. (2011) Test on Electrical Performance of 110kV Parallel Gap for Transmission Lines. Electric Power, 44, 7-10.
[10] Gu, T.L., Liu, S.Q., Zhao, G.L., et al. (2012) Research of Anti-Lightning Protective Gap Parallel with 220kV Insulator String. High Voltage Apparatus, 48, 116-120.
[11] Gu, S.Q. (2007) Characteristics of Long-Gap AC Arc Motion on Overhead Lines and Its Application Research. Tsinghua University, Beijing, 36-37.
[12] Sima, W.X., Tan, W., Yang, Q., et al. (2011) Long AC Arc Movement Model for Parallel Gap Lightning Protection Device with Consideration of Thermal Buoyancy and Magnetic Force. Proceedings of the CSEE, 31, 138-145.
[13] Lou, J., Sun, Q.Q. and Li, Q.M. (2013) Recovery Voltage Characteristics of Secondary Arc during Zero-Crossing Stage. High Voltage Engineering, 39, 2960-2966.
[14] Chen, W.J., Zeng, R. and He, H.X. (2013) Research Progress of Long Air Gap Discharge. High Voltage Engineering, 39, 1281-1295.
[15] Chen, W.J., Sun, Z.Y., Wang, X.L., et al. (2007) Research on the Parallel Gap of Lightning Protection of 35kV Overhead Transmission Lines. Grid Technology, 31, 23-24.
[16] Tan, W. (2011) Research on Parallel Gap Lightning Protection of Transmission Line Insulators. Chongqing University, Chongqing.
[17] Gu, S.Q., He, J.L., Chen, W.J., et al. (2006) Magnetic Force Computation for the Electric Arc of Parallel Gap Lightning Protection Device on Overhead Transmission Lines. Proceedings of the CSEE, 26, 140-145.
[18] Wang, W.R. (2010) Research on the Application of Parallel Gap Lightning Protection for Overhead Line Insulators. South China University of Technology.

Copyright © 2024 by authors and Scientific Research Publishing Inc.

Creative Commons License

This work and the related PDF file are licensed under a Creative Commons Attribution 4.0 International License.