The paper dwells on the unified power quality indexes characterizing the phenomenon of voltage unbalance in three-phase systems. Voltage unbalance is one of the commonest occurrences in the town mains of 0.38 kV voltage. The phenomenon describes as inequality of vector magnitude of phase voltage and shearing angle between them. Causes and consequences of the voltage unbalance in distribution networks have been considered. The algorithm, which allows switching one-phase load, has been developed as one of the methods of reducing the unbalance level. The algorithm is written in the function block diagram programming language. For determining the duration and magnitude of the unbalance level it is proposed to introduce the forecasting algorithm. The necessary data for forecasting are accumulated in the course of the algorithm based on the Function Block Diagram. The algorithm example is given for transforming substation of the urban electrical power supply system. The results of the economic efficiency assessment of the algorithm implementation are shown in conclusion. The use of automatic switching of the one-phase load for explored substation allows reducing energy losses (active electric energy by 7.63%; reactive energy by 8.37%). It also allows improving supply quality to a consumer. For explored substation the average zero-sequence unbalance factor has dropped from 3.59% to 2.13%, and the negative-sequence unbalance factor has dropped from 0.61% to 0.36%.
New materials and fabrication method (for example, cable production) aimed at reduction of the resistance value of a wire and, as consequence, energy loss saving [
Due to the constantly growing number of the connections of low power single-phase domestic and lighting loads, total power of which in the end becomes significant in its extent. The single-phase load is determining also because of the modern trends of urbane-planning, which is linked to a transfer of the industrial enterprises to the suburbs.
Under unbalanced conditions, the voltage deviation of consumers, the deterioration of electric loads as to all network elements, the liability degradation of electric equipment operation and electrical power supply system as a whole are observed [
In exit of the unbalance beyond limits set in normative documents the significant increase of supplementary losses is observed. The reduction of the voltage unbalance is appropriate even when it is within the permissible limits, because it
will result in a loss reduction in electrical networks and loads. The Refs. [
In this paper the balancing problem is considered not only as the means of the energy quality improvement, but also as the means of the efficiency and reliability improvement of the electrical power system as a whole. The subject of scientific research is the two-transformer substation of town electrical power supply system. The algorithm, which allows switching one-phase load, has been developed as one of a method of reducing the unbalance level. The algorithm is written in the function block diagram programming language. For determining the duration and magnitude of the unbalance level it is proposed to introduce the forecasting algorithm. The necessary data for forecasting is accumulated in the course of the algorithm based on the Function Block Diagram. The algorithm example is given for transforming substation of the urban electrical power supply system.
The outline of the paper is as follows: “Problem formulation” explores the main idea of the concept and the algorithm itself is defined in section “Algorithm description”. The real data measurements and simulation results are presented in section “Results and discussions”. Section “Conclusion” addresses the main benefits of the proposed concept.
The transformer substation of urban electrical power supply system is the subject of research. The transformer substation fragment simulated in the software complex is shown in
The motor load includes controlled induction and synchronous motors, capacitor voltage supply units, output capability of which remains constant when the voltage is changed.
The design of automated control system of unbalance in the distribution networks is one of a method of reducing the voltage unbalance. The use of such system will allow automatically remove the unbalance of three-phase system by the proportional redistribution of single-phase load in phases on the 0.4 kV substation feeder considering the forecasting data of unbalance occurrence.
The algorithm, which allows switching one-phase load, has been developed for the transformer substation. The single-phase transfer load sets as random variable in the range of 1% to 20% of each phase load. It is the obligatory condition―from phase to phase can be switched no more than 20% of the single-phase load. Operation algorithm and structure flow chart of the device is shown in
was used to design and test algorithm. The algorithm based on the Function Block Diagram (FBD), the result is the hardware-software complex performing the function of matching device (MD). The example of algorithm part based on FBD is shown in
The first functional unit is programed to determine the initial position of keys, i.e. determine the meaning of Xi, Yi, Zi. The second unit performs a function of determining the total load on every phase, which is calculated as follows:
S p h i = S i + X i ⋅ S l 1 + Y i ⋅ S l 2 + Z i ⋅ S l 3 ,
where Sphi is the power of every separate phase, Si is the constant load of every separate phase, Sli is the switched load. According to results, the next two units choose the maximum and minimum loaded phases to switch the load (from maximum to minimum). The functional unit of calculation of losses uses the following mathematical tools:
Δ S = S a v − S p h i − S l i , ,
further, the comparison unit perform the procedure and choose the minimal ( | Δ S → min | ). On one of the final step of the algorithm, the functional unit is programmed to set the range ±5% from the average power on phases. The control signal won’t be given on the valve keys in the range. The last step of the algorithm is the unit performing the switching. The introduction of forecast unit in the algorithm allows determining the length of time and significance of the unbalance level. The data obtained from the algorithm implementation, which is built on the FBD, is cumulative. Due to this the database to implement forecasting is formed. The forecasting time-frame is 25 minutes. The data analysis allows avoiding extra switchings, which cannot be justified from either an economic or technical point of view. The introduction of unit, which is programmed to set a turn-on delay, allows using the forecast data. The turn-on delay is equal to the forecasting time-frame.
As a forecast unit is used autoregressive moving-average model (ARMA (p,q))/Generalized autoregressive conditional heteroscedasticity (GARCH (p,q)), which is powerful tool to build accurate forecasts with a small forecasting time-frame. The ARMA-model generalizes two simpler models of time series: AR-model and MA-model. The ARMA-model is based on the fact that any series depend on past values, errors and past errors [
ARMA-model is described by the following equation:
y t = C + ε t + ∑ i = 1 p φ i ⋅ y t − j + ∑ j = 1 q θ j ⋅ ε t − j ,
where p and q are integers, that determine the model order, C is constant, {εt} is “white noise”, the sequence of independent and identically distributed random variables (as a rule, normal) with mean zero, φ i and θj are real numbers, autoregressive coefficients and coefficient of a moving average, respectively.
GARCH-process modifies the fact that current conditional variance depends on previous changes of the energy consumption and previous assessments of the conditional variance (“old news”).
With the help of GARCH(p,q) model can be calculated conditional variance, the equation of which σ t 2 = E t − 1 ( ε t 2 ) is
σ t 2 = K + ∑ i = 1 p G i ⋅ σ t − j 2 + ∑ j = 1 q A j ⋅ ε t − j ,
with restrictions of ∑ i = 1 p G i + ∑ j = 1 q A j < 1 , K > 0, Gi ≥ 0, Aj ≥ 0, where p is the
number of previous assessments of the energy consumption, that can affect the current assessment, q is the number of the last changes of the energy consumption that can affect the current consumption, K is constant, Gi are weight coefficients determining the extent of the previous assessments of the energy consumption on current value, Aj are weight coefficients determining the extent of the previous assessments of the energy consumption on current consumption, ε is the previous changes of the energy consumption.
The forecasting model was realized using the software STATISTIKA, which allows estimating general model GARCH.
As a result, the model ARMA(1,1)/GARCH(1,1) is obtained with the following parameters (
An analysis of the received data suggests a conclusion that all coefficients are significant as they exceed the error practically by an order of magnitude. All restrictions for the GARCH (p,q) model are implemented (К = 359,3306 > 0, G = GARCH(1) = 0.8837 > 0, A = ARCH(1) = 0.0134 > 0). Substituting these values, the following equations are obtained:
σ t 2 = 359.3306 + 0.8837 ⋅ σ t − i 2 + 0.0134 ⋅ ε t − j 2 y t = − 0.6399 + ε t + 0.4088 ⋅ y t − i + 0.1357 ⋅ ε t − j
An average for one day the use of balanced-to-unbalanced converter allows saving about 8% - 10% of the energy of the total consumption. In cash equivalents the saving is 30 - 40 rubles/day [
Parameters | ARMA(1,1) | Parameters | GARCH(1,1) |
---|---|---|---|
C | 0.6399 (2.081842) | K | 359.3306 125.989190 |
AR(1) | 0.4088 (0.079626) | GARCH(1) | 0.8837 (0.039658) |
MA(1) | 0.1357 (0.083431) | ARCH(1) | 0.0134 (0.003490) |
Without balanced-to-unbalanced converter | With balanced-to-unbalanced converter | |||
---|---|---|---|---|
∆WP, kWh | ∆WQ, kWh | ∆WP, kWh | ∆WQ, kWh | |
Power losses in transformers | 92.764 | 386.967 | 82.561 | 353.464 |
Power losses in cable lines 0.4 kV | 111.313 | 21.694 | 105.931 | 20.998 |
The total power losses | 204.076 | 408.661 | 188.492 | 374.461 |
and voltage unbalance in town distribution networks. The use of automatic single-phase switching device for the substation allows to reduce energy losses (active energy losses decreased by 7.63%, reactive energy losses decreased by 8.37%). It also allows improving quality of the power supply. For the substation being studied the average zero-sequence unbalance factor reduced from 3.59% to 2.13% (
This paper investigates the method of reducing the unbalance level in town mains of 0.38 kV. In this purpose, the algorithm, which allows switching one-phase load, is presented. The algorithm includes forecast unit to avoid extra switchings. The proposed framework practically is performed on the Functional Block Diagram. The simulation of a real transformer substation of urban electrical power supply system demonstrated that the use of the proposed algorithm allows reducing consumption and losses. Finally, the use of the presented optimization method allows improving quality of the power supply.
Shutov, E.A., Turukina, T.E. and Elfimov, I.I. (2018) Unbalance Level Regulating Algorithm in Power Distribution Networks. Energy and Power Engineering, 10, 65-76. https://doi.org/10.4236/epe.2018.102005