Safety Limits for Pre-Tension of Membrane Roofs on Closed Structure in Air Flow ()
1. Introduction
Membrane materials are usually used as enclosure materials (such as membrane roofs) or structural materials (such as inflatable membrane structures) in stadiums, architectural sketches and other buildings. These widely used membranes have small dead weight and low stiffness, which leads to extremely easy vibration under wind load. If the initial pre-tension of the membrane is too small, it may lead to instability of the membrane roof, and the membrane will be torn and destroyed due to excessive vibration amplitude. In history, there are many engineering cases of membrane roof damage. Atlanta Georgia Dome, Japan Xiongding Park membrane structure roof, Guangzhou Yihe Mountain Villa membrane structure, Jiaxing Pinghu Gymnasium membrane roof, etc. all suffer from instability and damage when the wind speed is lower than the design, which shows that the value of membrane pre-tension according to the current technical regulations of membrane structure cannot completely guarantee the safe use of membrane structure.
The stiffness of roofing membrane mainly comes from the initial tensile force applied to the membrane. Studies by Shen Shizhao, Wu Yue and other scholars have shown that [1]: When the flexible membrane structure is in a relaxed state, that is, when the pre-tension is insufficient, instability will occur, leading to the destruction of the membrane structure. For the study of instability and failure of membrane structure, in 2011, Zheng Zhoulian et al. determined the critical state of instability of small sag flat membrane structure and saddle membrane structure under wind load, and proved that the critical wind speed of instability is related to the initial pretension of membrane material [2] [3]; In 2015, Chen Zhaoqing et al. conducted aeroelastic model wind tunnel test of unidirectional tension membrane roof and discussed its instability mechanism [4]. In 2017, Liu et al. studied the stability of tensile membrane structure under wind load by Galerkin method, and obtained the main control factors to improve the stability of membrane structure [5]. In addition, many scholars have studied the wind-induced vibration response of membrane structures, but they have not quantitatively given the specific limits of pretension to prevent wind-induced damage [6]-[10]. The purpose of this paper is to determine the safe pretension limit of membrane roof in air flow field so as to avoid the occurrence of instability.
In this paper, the dynamic control equation of closed membrane roof under wind load is established, and the improved multi-scale method is used to solve it analytically. The closed expression of critical wind speed of instability is obtained by judging the criterion of critical condition of instability, and the inequality between site design wind speed and critical wind speed is established, and the safety pretension limit of closed membrane roof is obtained to prevent instability under specific wind field, which provides theoretical basis for determining the pretension in membrane structure design.
2. Derivation of Critical Wind Speed Expression for Instability of Membrane Roof
With the vibration of membrane roof, the transverse amplitude of membrane is relatively large, which is in the same order of magnitude as the thickness of membrane, showing a strong nonlinear state. However, most of the traditional nonlinear solution methods are only suitable for weak nonlinear systems, but not when the amplitude of membrane is large. Therefore, the improved multi-scale method is used to study the vibration of membrane.
2.1. Governing Equation of Vibration and Boundary Conditions
Let the length and width of the four-sided fixed membrane roof be a and b respectively; The pretension along the length direction is N0x, and the pretension along the width direction is N0y; The wind blows parallel to the membrane surface, as shown in Figure 1. Single-mode divergent instability characterized by large vibration will occur in the state of relaxation or insufficient pre-tension of roof membrane [2]. According to the test results carried out by Usenatsu, Kimoto et al. [11], it is found that the film does not tear when the single-mode divergent instability occurs, but only the vibration displacement amplitude jumps. Therefore, this paper assumes that the film is still in the linear elastic stage when the divergent instability occurs.
Figure 1. The membrane roof on closed structure.
When the roof membrane vibrates, the generalized external load includes wind load acting on the membrane surface, structural damping force and inertia force [2] [3]. In the process of membrane vibration, ignoring the influence of shear stress [12], the dynamic governing equations of roof membrane are as follows:
(1)
where h is the thickness of the film;
and
represent Young’s modulus of elasticity in the x-direction and y-direction, respectively; w represents the normal vibration displacement of the membrane material;
is the surface density of the film material; c represents the damping coefficient of membrane material;
denotes the stress function.
The membrane roof is fixed on four sides, so the boundary conditions are:
,
(2)
2.2. Solution of Vibration Governing Equation
Since the initial surface function of the membrane roof is
, the surface equation of the roof under wind load is
(3)
The initial curvature of the roof membrane and the curvature during vibration are
(4)
Let the solution of the governing equation be [12]
(5)
In reference [2], the partial differential equation of wind-induced vibration of membrane roof is obtained as follows:
(6)
where,
Equation (6) is integrated using the Bubnov-Galerkin method, yields,
(7)
The integration region in Equation (7) is
.
Simplifying Equation (7), yields,
(8)
where
In Equation (8),
, Let
, according to the
calculation principle of improved multi-scale method [13], take the perturbation
parameters as
, then, Equation (8) can be simplified
as:
(9)
where,
Let ω be the vibration frequency of the roof membrane, and expand
near
into a power series of ε, that is,
(10)
Letting,
(11)
Then,
(12)
Expand ω2 into a power series of ε [14],
(13)
(14)
The solution of Equation (9) can be assumed to be
(15)
where
.
The differential operators can be obtained as follows:
(16)
By substituting Equations (11)-(13) and (16) into Equation (9) and collating, we can obtain:
(17)
Expand Equation (17), let the coefficients of each power of
in the equation be zero, yields,
(18)
The solution of the first equation in the system of Equation (18) can be
(19)
By substituting Equation (19) into
, yields:
(20)
Where cc is a conjugate complex number, let:
(21)
Solving Equations (21), yields
(22)
Let
, then substitute it into Equation (22) and separate the imaginary
and real parts,
(23)
substitute
into Equation (19), yields:
(24)
It can be obtained from Equations (24) and (14) that under the first-order approximation condition
(25)
Combining Equations (23) and (25), yields:
(26)
By substituting Equation (26) into Equation (23) and omitting the higher-order terms, yields:
(27)
The existing research results show that when the membrane roof reaches the critical state of instability, the frequency of the characteristic equation of the system approaches zero [2] [3]. i.e.:
(28)
where f is the vibration amplitude of the membrane material.
.
From Equation (28), the critical wind speed when the roof membrane material is instable can be obtained as follows:
(29)
where f is the vibration amplitude, that is, the vibration amplitude corresponding to the critical wind speed of instability. It shows that the critical wind speed is related to the vibration amplitude. Because the geometric nonlinear influence of membrane is considered, the stiffness of membrane will change with the change of amplitude in the vibration process, which will affect the stability of the structure to a certain extent, which is consistent with the existing research results. When f → 0, the critical wind speed calculated according to the small deflection theory can be obtained.
3. Minimum Pre-Tension of Membrane Roof
The principle of determining the safety pre-tension of the membrane roof under a specific site is that under the local design maximum wind speed, the membrane roof will not be instable and damaged, that is, the local design maximum wind speed is less than or equal to the critical wind speed of instability, that is:
(30)
Substituting Equation (29) into Equation (30), yields:
(31)
where, V is the local design wind speed.
(32)
Simplify Equation (32), yields:
(33)
Equation (33) is the formula for determining the safety pretension limit of membrane roof to prevent instability. When the span ratio of roof membrane is determined, the safe pretension value can be obtained.
Let
,
,
,
,
.
The results of safety pretension limits of membrane roofs in a certain area are shown in Table 1.
Table 1. Safety pretension limit of membrane roof.
Design Return Period/Years |
Vcr/(m/s) |
Roof length/(m) |
Roof width/(m) |
Safety pretension limit/(kN/m) |
10 |
20 |
5 |
10 |
1.223 |
10 |
10 |
1.434 |
20 |
10 |
1.245 |
50 |
25.3 |
5 |
10 |
1.957 |
10 |
10 |
2.295 |
20 |
10 |
1.993 |
100 |
26.83 |
5 |
10 |
2.200 |
10 |
10 |
2.581 |
20 |
10 |
2.241 |
4. Conclusions
In this paper, the traditional multi-scale method is improved to solve the critical state of instability of membrane roof. In order to avoid the instability of the roof during the design return period, the critical wind speed of instability should not be less than the local design wind speed, so that the calculation formula of the minimum pretension of the roof film to prevent instability in different return periods of a specific wind field is obtained, and the following conclusions are obtained.
1) The critical wind speed of nonlinear wind-induced instability of membrane roof is related to membrane pretension, geometric size, density and vibration amplitude.
2) The safety pretension limit of membrane roof to prevent instability is related to the design wind speed and membrane geometry. This paper supplements the specific requirements on the value of pretension in the technical specification of membrane structure (CECS158: 2015) [15], and provides a theoretical basis for engineering designers to reasonably design membrane structure.