The Research on Grounding Protection for 110kV Resistance Grounding Distribution System ()
Shan Sun,
Guo Zeng,
Xiaozang He,
Yanping Lv,
Xinyi Li
Huangshi Power Supply Company, Huangshi, China.
Wuhan University, Wuhan, China.
DOI: 10.4236/epe.2013.54B168
PDF HTML
5,266
Downloads
6,545
Views
Citations
Abstract
Using the neutral grounding method by the resistance in
110 kV system, it can limit the
voltage sag and short circuit current when one-phase grounding fault occurred,
but it will change the sequence of the network structure and parameters. This
paper analyzes the size and distribution of zero sequence voltage and current
when one-phase grounding fault occurred in the 110 kV resistance grounding
system, and puts forward the grounding protection configuration setting
principle of this system combining the power supplying characteristics of 110 kV distribution network. In a reforming substation as an example,
the grounding protection of 110 kV lines and transformer have been
set and calculated.
Share and Cite:
S. Sun, G. Zeng, X. He, Y. Lv and X. Li, "The Research on Grounding Protection for 110kV Resistance Grounding Distribution System,"
Energy and Power Engineering, Vol. 5 No. 4B, 2013, pp. 877-880. doi:
10.4236/epe.2013.54B168.
Conflicts of Interest
The authors declare no conflicts of interest.
References
[1]
|
N. T. Li, K. Li and D. M. Zhou, “Disscussion on Voltage Dropping of Power Supply and Distribution System of Baosteel, Metallurgical power, Vol. 5, No. 147, 2011,pp. 1-3.
|
[2]
|
Y. Z. He and Z. Y. Wen, “Power System Analysis,” Huazhong University of Science and Technology Press, Wuhan , China.
|
[3]
|
B. H. Zhang, “Power System Relay Protection,” China Electric Power Press,Beijing, China, 2011.
|