Energy and Power Engineering

Volume 5, Issue 4 (July 2013)

ISSN Print: 1949-243X   ISSN Online: 1947-3818

Google-based Impact Factor: 0.73  Citations  h5-index & Ranking

Research on Co-phase Power Supply Test System

HTML  Download Download as PDF (Size: 355KB)  PP. 522-526  
DOI: 10.4236/epe.2013.54B100    4,498 Downloads   5,748 Views   Citations

ABSTRACT

Co-phase power supply system can solve the problems of power quality of heavy unbalanced three phase, large harmonics and reactive power and cancel neutral section in electric railway power supply system. In order to do further research, a co-phase power supply test system is proposed. By mean of analyzing on structures and principles of YNvd transformer, integrated power flow controller (IPFC) and simulation load, establishing control strategy on IPFC and simulation load, the system is simulated dynamically. The results illustrate that the scheme can well simulate co-phase system, and the negative sequence is eliminated, harmonic and reactive power are real-timely compensated in system.

Cite this paper

Y. Zhao, Q. Li, Y. Xia and Z. Shu, "Research on Co-phase Power Supply Test System," Energy and Power Engineering, Vol. 5 No. 4B, 2013, pp. 522-526. doi: 10.4236/epe.2013.54B100.

Copyright © 2020 by authors and Scientific Research Publishing Inc.

Creative Commons License