Simulation Study of Dynamic Fault Recovery Performance of VSC-HVDC System

HTML  Download Download as PDF (Size: 133KB)  PP. 15-19  
DOI: 10.4236/epe.2013.53B004    5,293 Downloads   6,872 Views  Citations

ABSTRACT

The fault recovery of VSC-HVDC transmission system is often influenced by many factors, such as the reactive power compensation characteristics of the inverter and the dynamic performance of DC controllers. In this paper, the PSCAD/ EMTDC simulation tool is used to study the dynamic recovery performance of VSC-HVDC system for several different var compensating devices in VSC-HVDC inverter-Fixed capacitor (FC), Static Var compensator (SVC), and Static synchronous compensator (STATCOM) when VSC-HVDC is subject to various faults, including three phase groundings, single phase grounding and three phase breakings. The result shows that the recovery process of the whole system will be slowed down due to its negative influence on the strength of AC power system with the application of SVC, while the STATCOM can improve VSC-HVDC recovery performance greatly for its advantages over other compensating devices in areas such as voltage support ability and DC power recovery.

Share and Cite:

Z. Cheng, X. Wang, X. Wu, G. Du and F. Li, "Simulation Study of Dynamic Fault Recovery Performance of VSC-HVDC System," Energy and Power Engineering, Vol. 5 No. 3B, 2013, pp. 15-19. doi: 10.4236/epe.2013.53B004.

Copyright © 2024 by authors and Scientific Research Publishing Inc.

Creative Commons License

This work and the related PDF file are licensed under a Creative Commons Attribution 4.0 International License.