TITLE:
Energization of a Half-Wavelength Transmission Line - Pre-Operational Transients Studies
AUTHORS:
Camilo Machado Jr, Marcelo Maia, Eden Carvalho Jr, Maria C. Tavares, João B. Gertrudes, Elson C. Gomes, Walmir Freitas, Marcos A. Paz, Fernando A. Moreira, Carlos A. Floriano, Vanderlei G. Machado, Aniela M. Mendes
KEYWORDS:
Electromagnetic Transients; Half-wavelength Transmission; AC-Link; Energization Test; Dynamic Analysis; TRV; Faults
JOURNAL NAME:
Energy and Power Engineering,
Vol.5 No.4B,
November
21,
2013
ABSTRACT:
In the present paper the main results of the
pre-operational studies related to the energization maneuver of a
Half-Wavelength Transmission Line (AC-Link), are presented. The simulations
were performed in PSCAD with actual Brazilian system data. Specifically the
following studies were performed: electromagnetic transient studies of energization
maneuver considering no fault and the occurrence of fault along the trunk;
dynamic analysis of generator units that will energize the AC-Link; TRV on the
circuit-breaker that will energize the trunk. The main conclusion is that the
AC-Link energization experiment can be implemented without jeopardizing or
causing time-life reduction of the equipment involved in the experiment, which
comprises the generator unit that will energize the trunk, the step-up
transformer, the arresters that will be kept during the experiments, as well as
the circuit-breaker that will energize and then trip the AC-Link.