The Resuming Insulation Discharge Failure and Conductor Overheating Failure Judgment Method of SF6 Electrical Equipment
Xiansheng ZHUANG, Zhi LI, Chengji HUANG
.
DOI: 10.4236/epe.2009.12019   PDF    HTML     5,646 Downloads   8,966 Views   Citations

Abstract

Through the long time track examination and disintegration to SF6 circuit breaker, we obtain the massive monitor data and massive pictures. The criteria of resuming insulation discharge failure conforming to CSO2/CH2S>7, is quite broad to SO2 and the H2S concentration permission. Even if it reaches 100µL/L, it will not be in danger immediately to the safe operation of equipment. We may plan, arrange, and overhaul calmly. When obtaining the bare conductor overheating failure, it has not involved the resuming insulation. We may use the resuming insulation discharge failure criterion.

Share and Cite:

X. ZHUANG, Z. LI and C. HUANG, "The Resuming Insulation Discharge Failure and Conductor Overheating Failure Judgment Method of SF6 Electrical Equipment," Energy and Power Engineering, Vol. 1 No. 2, 2009, pp. 122-127. doi: 10.4236/epe.2009.12019.

Conflicts of Interest

The authors declare no conflicts of interest.

References

[1] IEC 60480–2004, “Guidelines for the checking and treat- ment of sulfur hexafluoride (SF6) taken from electrical equipment and specification for its re-use”, 2004.
[2] X. S. Zhuang, “The examination and judgment of SF6 elec-trical equipment discharge failure,” Asia-Pacific Power and Energy Engineering Conference (APPEEC’09), 2009.

Copyright © 2024 by authors and Scientific Research Publishing Inc.

Creative Commons License

This work and the related PDF file are licensed under a Creative Commons Attribution 4.0 International License.