Reassessment of Permissible Negative Sequence Current for Power Plant Operation of Taipower
Ping-heng Ho, Chi-jui Wu, Chung-liang Chang, Yuin-hong Liu
.
DOI: 10.4236/epe.2010.24039   PDF    HTML     5,786 Downloads   10,166 Views   Citations

Abstract

The N3 power plant of Taipower is located in the southern tip of Taiwan and connected to the power pool by four out-linking 345-kV overhead transmission circuits. There are two 951-MW generators. Each generator occupied 11% of the system peak load in 1985 when the generator was in commercial operation. Since Taipower is an isolated system, at the N-2 conditions, those generators were reduced to 75% loading to protect the power system. By the way, to avoid damage of negative sequence current (NSC), the limits of the N3 power plant are stricter than those in the IEEE Standard. However, in 2010, the capacity ratio of each generator in the plant to the system peak load has been reduced to 3% only. To increase the economic benefit of those generators, it is required to reassess the operation limits of NSC. EMTP was used to calculate the levels of NSC from the out-linking transmission circuits. From the results of this study, the effects of NSC could be ignored when the four out-linking circuits are in N-0, N-1, and N-2 conditions. The generators can be operated in full loading under these conditions. The modifications to the NSC limits of the N3 power plant are also suggested.

Share and Cite:

P. Ho, C. Wu, C. Chang and Y. Liu, "Reassessment of Permissible Negative Sequence Current for Power Plant Operation of Taipower," Energy and Power Engineering, Vol. 2 No. 4, 2010, pp. 271-282. doi: 10.4236/epe.2010.24039.

Conflicts of Interest

The authors declare no conflicts of interest.

References

[1] W. H. Kersting, “Gauses and Effect of Unbalanced Voltages Serving an Induction Moter,” IEEE Transactions on Industry Applications, Vol. 37, No. 1, January/February 2001, pp. 165-170.
[2] G. Chicco, P. Postolache and C. Toader, “Analysis of Three-Phase Systems with Neutral under Distorted and Unbalanced Conditions in the Symmetrical Component- Based Framework,” IEEE Transactions on Power Delivery, Vol. 22, No. 1, January 2007, pp. 674-683.
[3] W. V. Lyon, “Reactive Power and Unbalanced Circuits,” Electrical World, Vol. 75, No. 25, June 1920, pp. 1417- 1420.
[4] M. H. Hesse and J. Sabath, “EHV Double-Circuit Untransposed Transmission Line-Analysis and Tests,” IEEE Transactions on Power Application System, Vol. PAS-90, No. 3, May 1971, pp. 984-992.
[5] P. Pillay and M. Manyage, “Definitions of Voltage Unbalance,” IEEE Power Engineering Review, May 2001, pp. 50-51.
[6] M. M. Adibi, D. P. Milanicz and T. L. Volkmann, “Asymmetry Issues in Power System Restoration,” IEEE Transactions on Power Systems, Vol. 14, No. 3, August 1999, pp. 1085-1091.
[7] L. S. Czarnecki, “Power Related Phenomena in Three- Phase Unbalanced Systems,” IEEE Transactions on Power Delivery, Vol. 10, No. 3, July 1995, pp. 1168- 1176.
[8] J. Ma and F. P. Dawalibi, “Analysis and Mitigation of Current Unbalance Due to Induction in Heavily Loaded Multicircuit Power Lines,” IEEE Transactions on Power Delivery, Vol. 19, No. 3, July 2004, pp. 1378-1383.
[9] J. E. Barkle and W. E. Glassburn, “Protection of Generators against Unbalanced Current,” AIEE Transactions on Part III, Vol. 72, 1953, pp. 282-285.
[10] S.-L. Chen, R.-J. Li and P.-H. Hsi, “Traction System Unbalance Problem-Analysis Methodologies,” IEEE Transactions on Power Delivery, Vol. 19, No. 4, October 2004, pp. 1877-1882.
[11] A. P. S. Meliopoulos and F. Zhang, “Multiphase Power Flow and State Estimation for Power Distribution Systems,” IEEE Transactions on Power Systems, Vol. 11, No. 2, May 1996, pp. 939-946.
[12] F. J. Alcantara and P. Salmeron, “A New Technique for Unbalance Current and Voltage Estimation with Neural Networks,” IEEE Transactions on Power Systems, Vol. 20, No. 2, May 2005, pp. 852-858.
[13] Z. Emin and D. S. Crisford, “Negative Phase-Sequence Voltages on E&W Transmission System,” IEEE Transactions on Power Delivery, Vol. 21, No. 3, July 2006, pp. 1607-1612.
[14] Shaw Technologies, Inc., PSS/E 30 Online Documentation, August 2004.
[15] Leuven EMTP Center (LEC), “Alternative Transients Program (ATP) Rule Book,” July 1987.
[16] J. A. Martinez, B. Gustavsen and D. Durbak, “Parameter Determination for Modeling System Transients-Part I: Overhead Lines,” IEEE Transactions on Power Delivery, Vol. 20, No. 3, July 2005, pp. 2038-2044.
[17] J. A. Martinez, R. Walling, B. A. Mork, J. M. Arnedo, and D. Durbak, “Parameter Determination for Modeling System Transients-Part III: Transformers,” IEEE Transactions on Power Delivery, Vol. 20, No. 3, July 2005, pp. 2051-2062.
[18] W. D. C. Boaventura, A. Semlyen, M. R. Iravani and A. Lopes, “Sparse Network Equivalent Based on Time- Domain Fitting,” IEEE Transactions Power Delivery, Vol. 17, No. 1, January 2002, pp. 182-189.
[19] M. A.-Rahman, A. Semlyen, and M. R. Iravani, “Two- Layer Network Equivalent for Electromagnetic Transients,” IEEE Transactions on Power Delivery, Vol. 18, No. 4, October 2003, pp. 1328-1335.
[20] IEEE Guide for AC Generator Protection, IEEE Standard C37.102-2006, February 2007.
[21] EEE Standard for Cylindrical-Rotor 50Hz and 60 Hz Synchronous Generators Rated 10 MVA and Above, IEEE Standard C50.13-2005, February 2006.
[22] W. S. Meyer and T.-H. Liu, “Electro-Magnetic Transients Program (EMTP) Theory Book,” Bonneville Power Administration, February 1986.

Copyright © 2024 by authors and Scientific Research Publishing Inc.

Creative Commons License

This work and the related PDF file are licensed under a Creative Commons Attribution 4.0 International License.