The Research on Grounding Protection for 110kV Resistance Grounding Distribution System ()
ABSTRACT
Using the neutral grounding method by the resistance in
110 kV system, it can limit the
voltage sag and short circuit current when one-phase grounding fault occurred,
but it will change the sequence of the network structure and parameters. This
paper analyzes the size and distribution of zero sequence voltage and current
when one-phase grounding fault occurred in the 110 kV resistance grounding
system, and puts forward the grounding protection configuration setting
principle of this system combining the power supplying characteristics of 110 kV distribution network. In a reforming substation as an example,
the grounding protection of 110 kV lines and transformer have been
set and calculated.