Design of a Control Device for Synthetic Making Test Based on Pre-Arcing Current Detection and Phase Control
Zhengyang ZHOU, Minfu LIAO, Xingming FAN
.
DOI: 10.4236/jemaa.2009.14043   PDF    HTML     4,993 Downloads   8,788 Views   Citations

Abstract

The synthetic making test has been widely used in evaluating the break ability of high-voltage circuit breaker. However, the test research and application are still inadequate, especially in the condition of rated voltage. According to the realistic conditions of test stations in China, a control device based on pre-arcing current detection and phase control is proposed in this paper. A sample of the control device made up of DSP TMS320LF2407A is fabricated, in which the CPLD MAX7064 is used to transmit signals for EMC design. It can be applied in full voltage synthetic making test at a level of 126kV/63kA. The test results show that, it is accurate to control the making phase of the applied voltage, whether the closing is demanded at voltage peak or zero.

Share and Cite:

Z. ZHOU, M. LIAO and X. FAN, "Design of a Control Device for Synthetic Making Test Based on Pre-Arcing Current Detection and Phase Control," Journal of Electromagnetic Analysis and Applications, Vol. 1 No. 4, 2009, pp. 279-283. doi: 10.4236/jemaa.2009.14043.

Conflicts of Interest

The authors declare no conflicts of interest.

References

[1] R. P. P. Smeets and W. A. van der Linden, “Verification of the short-circuit current making capability of high- voltage switching devices,” IEEE Transactions on Power delivery, Vol. 16, No. 4, pp. 611–618, 2001.
[2] Discussion Group 13, “Synthetic circuit for making tests,” CIGRE Conference, pp. 444–445, 1966.
[3] CIGRE WG 13.04, “Requirements for testing making performance of high-voltage circuit breakers at reduced applied voltage,” Electra, Vol. 163, No. 6, pp. 27–33. 1979.
[4] IEC60427, “Synthetic testing of high-voltage alternating- current circuit breakers,” 2000
[5] GB 1984–2003, “High-voltage alternating-current circuit- breakers.”
[6] B L Sheng, “Design consideration of weil-dobke synthetic testing circuit for the interrupting testing of HV AC breakers,” IEEE Power Engineering Society Winter Meeting, Vol. 1, No. 28, pp. 295–299, 2001.
[7] X. M. Fan, J. Y. Zou, and J. Y. Cong, “Research on the measurement and controlling system for synthetic making test of high-voltage circuit breakers at full voltage,” 6th International Symposium on Test and Measurement, Vol. 3, pp. 2709–2712, 2005.
[8] X. P. Li, C. Zhao, L. Y. Li, J. Y. Zhou and T. Meng, “The test system of pulse high current in the reconnection electromagnetic gun,” 6th International Symposium on Test and Measurement, Vol. 3, pp. 2847–2850, 2005.
[9] J. Y. Zou, X. Y. Duan, and T. Zhang, “The simulating calculation and experimental research of Rogowski coil for current measurement,” Transactions of China Electrotechnical Society, Vol. 16, No. 1, pp. 82–84, Feburay 2001.
[10] X. M. Fan, J. Y. Zou, E. Y. Dong, and J. Y. Cong, “Control strategy of synthetic making test for high voltage circuit breakers at full voltage and its realization,” Power system technology, Vol. 29, No. 17, pp. 8–13, 2005.

Copyright © 2024 by authors and Scientific Research Publishing Inc.

Creative Commons License

This work and the related PDF file are licensed under a Creative Commons Attribution 4.0 International License.