Dual-loop Control Strategy for Grid-connected Inverter with LCL Filter

Abstract

As to the concrete topology of three-phase LCL type grid-connected inverter with damping resistance, mathematical model was deduced in detail, using method of equivalent transformation to the structure diagram, damping resistance was virtualized, mathematical model under the DQ frame that can realize decoupling control was established, a dual-loop control strategy for grid-connected inverter with LCL filter was proposed, the system stability was analyzed and the design method of controller was given. The proposed method overcame the flaws of loss increase, efficiency reduce and cost increase which were caused by damping resistance in LCL type grid-connected inverter, the system efficiency and power supply quality of the output were improved. Feasibility and effectiveness of the new method were validated by simulation and experimental results.

Share and Cite:

Q. Peng, H. Pan, Y. Liu and L. Xiang, "Dual-loop Control Strategy for Grid-connected Inverter with LCL Filter," Energy and Power Engineering, Vol. 5 No. 4B, 2013, pp. 97-101. doi: 10.4236/epe.2013.54B019.

Conflicts of Interest

The authors declare no conflicts of interest.

References

[1] Y. Q. Wang, F. J. Wu, L. Sun, et al., “Optimized Design of LCL Filter for Minimal Damping Power Loss,” Proceedings of the CSEE, Vol. 30, No. 27, 2010, pp. 90-95.
[2] M. Liserre, A. Dell'Aquila and F. Blaabjerg, “Stability Improvements of an LCL-filter Based Three-phase Active Rectifier,” IEEE Annual Power Electronics Specialists Conference, Cairns, 2002.
[3] X. H. Wang, X. B. Ruan and S. W. Liu, “Control Strategy for Grid-connected Inverter to Suppress Current Distortion Effected by Background Harmonics in Grid Voltage,” Proceedings of the CSEE, Vol. 31, No. 6, 2011, pp. 7-14.
[4] C. H. Zhang, Y. Ye, A. Chen, et al., “Research on Grid-connected Photovoltaic Inverter Based on Output Current Control,” Transactions of China Electrotechnical Society, Vol. 22, No. 8, 2007, pp. 41-45.
[5] T. C. Y. Wang,Z. H .Ye,G. Sinha,et al., “Output Filter Design for a Grid-interconnected Three-phase Inverter,” IEEE PESC’03, Acapulco, Mexico, 2003.
[6] Z. Y. Xu, A. G. Xu and S. J. Xie, “Dual-loop Grid Current Control Technique for Grid-connected Inverter Using an LCL Filter,” Proceedings of the CSEE, Vol. 29, No. 27, 2009, pp. 36-41.
[7] M. Malinowski and S. Bernet, “A Simple Voltage Sensorless Active Damping Scheme for Three-phase PWM Converters with an LCL Filter,” IEEE Transactions on Industry Electronics, Vol. 55, No. 4, 2008, pp. 1876-1880.
[8] Ji Bao-jian, F. Hong and J. F. Zhao, “A Non-isolated Three-level Dual Buck Photovoltaic Grid-connected Inverter,” Proceedings of the CSEE, Vol. 32, No. 12, 2007, pp. 7-13.
[9] B. C. Wang, X. Q. Guo, Q. Mei, et al., “DC Injection Control for Transformerless PV Grid- connected Inverters,” Proceedings of the CSEE, Vol. 29, No. 36, 2009, pp. 23-28.
[10] F. Liu, S. X. Duan and X. M. Zha, “Design of Two Loop Controller in Grid-connected Inverter with LCL Filter,” Proceedings of the CSEE, Vol. 29, No. S1, 2009, pp. 234-240.

Copyright © 2024 by authors and Scientific Research Publishing Inc.

Creative Commons License

This work and the related PDF file are licensed under a Creative Commons Attribution 4.0 International License.